AHU-VAH series

The models of VAH series units are marked by air flow. From 1500m3/h to 36000m3/h, there are nearly 30 sizes. The air handling unit can be matched with a single fan, double fans or three fans. Users can choose models by required airflow and external static pressure. The series units can be installed horizontally, vertically or on ceilings.
Note: Heaters, humidifiers and inverter controllers are available as optional components.

Technical Specifications of Air Handling Unit VAH Series

 Suspended Type Specifications (1)  Suspended Type Specification (2)  Horizontal Type Specifications (1) Horizontal Type Specifications (2)   Vertical Type Specifications (1)    Vertical Type Specifications(2)

  

A.Suspended Type
1. Suspended Type Specifications (1) (Return Air Condition)

No. Model Air Flow (m3/h) Cooling Capacity (KW) Cooling Capacity (BTU X10-3) Heating Capacity (KW) Heating Capacity (BTU X10-3) Water flow (l/s) Water Resis- tance (kPa) Noise dB(A) Fan Motor Power (kw) Fan Total Pres- sure (Pa) External Static Pres- sure (Pa) Net Weight (kg)
1 1.5A 4Rows 1500 8.37 25.31 12.31 37.23 0.40 4.3 ≤58 0.37 310 230 75
6Rows 12.40 37.50 16.38 49.53 0.60 7.7 310 210 80
2 02A 4Rows 2000 10.81 32.69 17.25 52.16 0.52 6.8 ≤58 0.45 330 250 85
6Rows 16.02 48.44 21.41 64.74 0.77 9.5 330 230 90
3 2.5A 4Rows 2500 14.07 42.55 21.90 66.23 0.68 13.2 ≤58 0.45 360 280 90
6Rows 20.55 62.14 26.98 81.59 0.98 18.4 360 260 95
4 03A 4Rows 3000 17.67 53.43 26.92 81.41 0.85 19.8 ≤58 0.55 350 270 103
6Rows 25.15 76.05 32.71 98.92 1.20 25.6 350 250 113
5 3.5A 4Rows 3500 18.97 57.37 30.21 91.36 0.92 22.7 ≤60 0.75 390 310 113
6Rows 28.21 85.31 37.56 113.58 1.35 29.4 390 290 123
6 04A 4Rows 4000 22.19 67.10 34.96 105.72 1.07 24.6 ≤60 0.75 360 280 120
6Rows 32.71 98.92 43.17 130.55 1.57 31.2 360 260 132
7 04B 4Rows 4000 23.89 72.24 36.13 109.26 1.15 24.6 ≤60 0.45*2 330 250 130
6Rows 31.26 94.53 42.35 128.07 1.50 31.2 330 230 140
8 05A 4Rows 5000 28.55 86.34 44.23 133.75 1.37 21.8 ≤62 1.5 400 320 140
6Rows 41.17 124.50 54.09 163.57 1.97 27.5 400 300 155
9 05B 4Rows 5000 30.33 91.72 49.67 150.20 1.45 34.4 ≤62 0.45*2 360 280 145
6Rows 41.50 125.50 50.71 153.35 1.98 40.7 360 260 165
10 06A 4Rows 6000 32.91 99.52 50.50 152.71 1.48 28.8 ≤62 1.5 350 270 150
6Rows 47.63 144.03 63.01 190.54 1.92 44.6 350 250 170
11 06B 4Rows 6000 32.63 98.67 51.75 156.49 1.57 42.4 ≤62 0.55*2 350 270 155
6Rows 48.07 145.36 64.08 193.78 2.30 51.5 350 250 185
12 07B 4Rows 7000 37.51 113.43 55.92 169.10 1.80 34.6 ≤64 0.75*2 390 310 170
6Rows 56.03 169.43 74.93 226.59 2.68 46.3 390 290 190
13 08B 4Rows 8000 44.34 134.08 69.92 211.44 2.12 40.6 ≤64 0.75*2 360 280 195
6Rows 65.20 197.16 86.21 260.70 3.12 48.7 360 260 225
14 10B 4Rows 10000 54.69 165.38 86.65 262.03 3.62 45.6 ≤66 1.5*2 400 320 210
6Rows 80.86 244.52 107.14 323.99 3.87 51.2 400 300 240
15 12B 4Rows 12000 58.03 175.48 97.42 294.60 2.78 46.9 ≤68 1.5*2 350 270 235
6Rows 90.35 273.22 123.67 373.98 4.32 53.1 350 250 270
16 15B 4Rows 15000 96.17 290.82 136.79 413.65 3.23 49.3 ≤68 2.2*2 470 390 290
6Rows 119.54 361.49 162.17 490.40 5.21 57.8 470 370 330
17 15C 4Rows 15000 96.32 291.27 137.87 416.92 3.28 49.3 ≤68 1.5*3 400 320 310
6Rows 120.45 364.24 162.30 490.80 5.28 57.8 400 300 350
 

Note: A:one fan, B: two fans, C: three fans

Standard Condition (Return Air Condition)
Cooling Standard Condition: Entering air temperature: 27℃D.B., 19.5℃W.B.
                                                     Entering water temperature: 7℃, leaving water temperature: 12℃
Heating Standard Condition: Entering air temperature: 21℃ D.B.
                                                     Hot water entering temperature: 60℃

Facing air return opening, connection pipe on the left is left style; connection pipe on the right is right style.

 

Optional accessories
★ Electrical heater         ★ Hot water heating coil      ★ Medium efficiency filtration
★ Wet film humidifier    ★ Dry steam humidifier        ★ Electrical protection device

Our Technical Partners


Coldcare Nigeria Limited is in technical partnership with acclaimed world leaders in related engineering services. This has helped us in the areas of training as well as research and development. This way, we are able to remain relevant and up-to-date in the ever-evolving engineering world

Read More...

Our Clients...


Our success is vested in our client's success  and we do our best to keep their satisfactions as our paramount goal.

 Among our highly esteemed clients are  Airtel Nigeria, Nigerian Bottling Company Plc, Reftech A/S, Gurara Bottling Company Limited, Hassan Plastics Limited, 


Read More...

Health Safety & Environment


COLDCARE NIGERIA LIMITED places high premium on Health, Safety and Environment (HSE). Our policy makes it mandatory for everyone who works for the company, Including contractual to adhere strictly to HSE performance standards.

Read More...

OUR VISION

Our Vision is to be a household name of international standard in the provision of quality engineering products and services.

  OUR MISSION:

To keep to the ideal of high ethical standards in providing quality and efficient services to our customers at reasonable cost